METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-135 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
The battery room shall contain provisions for housing batteries for communications
battery/rectifier plant and UPS Module/battery system.
9.16.10 Yard Control Tower Equipment
Provide a train dispatcher console in the Yard Control Tower identical to the train
dispatcher console at central control with the following services available:
A. Yard operations radio channel.
B. Emergency operations radio channel.
C. Transmit amplifiers and receive amplifiers, if required, shall be provided in the
Yard Control Tower communications equipment room.
D. Supervision, base station disable, voting control, patching, and other radio
facilities management control shall be performed by the communications
controller at central control.
9.17 YARD COMMUNICATIONS
9.17.1 General
The functionality of the various communications subsystems is described in other
sections of this document. Only the specific application of subsystems to the Yard
and its buildings is described in this subsection.
9.17.2 Communications (COMM) Equipment Room
The Communications Equipment Room shall be located in the vehicle maintenance
shop building. All terminal equipment for communication circuits to, from and within
the Yard shall be installed at this location.
All communications Yard duct banks and Yard-to-mainline transitional
communications duct banks shall terminate in a cable vault under or adjacent to the
Communication Equipment Room and have at least 20% separate conduit capacity.
9.17.3 CTS
The fiber optic and PCM multiplex CTS terminals for the Central Control/Yard
backbone line shall be located in the C&S room (reference Cable Transmission
Systems Backbone System).
Local distribution throughout the Yard and associated buildings shall be by standard
telephone cables as outlined in Cable Transmission Systems Backbone and Local
Distribution - Metallic Pairs. Main feeder cables shall be provided to major buildings,
e.g., Maintenance of Way, when they are present.
9.17.4 Telephone Service
All Yard telephone service (ATEL, ETEL and MTEL) shall be provided from the
appropriate Yard Metro private telephone system. Functionally, all services shall
operate as described in the telephone system with the exception that ETEL circuits
within the Yard complex shall ring to the Yard control room. Additionally, if the call is
not answered after three rings, the call shall be automatically forwarded to the
central control emergency reporting position.
9.17.5 Public Address